EasyManua.ls Logo

ProSoft Technology PLX3x Series

ProSoft Technology PLX3x Series
215 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EIP Protocol PLX3x Series Multi-Protocol Gateways
User Manual
Page 78 of 215 ProSoft Technology, Inc.
January 25, 2018
SLC5/05 Read Commands
Read commands transfer data to the SLC processor from the gateway. The
following diagram shows an example rung to execute a read command.
1 Set the READ/WRITE parameter to READ. The gateway supports a TARGET
DEVICE parameter value of 500CPU or PLC5.
2 In the MSG object, click SETUP SCREEN in the MSG object to complete the
configuration of the MSG instruction. This displays the following dialog box.
3 Set the TARGET DEVICE DATA TABLE ADDRESS to a valid file element (such
as, N11:0) for SLC and PLC5 messages.
4 Set the MULTIHOP option to YES.

Table of Contents

Related product manuals