Diagnostics and Troubleshooting MVI56-PDPMV1 ♦ ControlLogix Platform
User Manual PROFIBUS DPV1 Master
Page 180 of 251 ProSoft Technology, Inc.
Debug Access After Power Up
LED Behavior After Power Up
LEGACY Ladder loaded to
processor (module is inserted in
configured slot)
MSTR STAT= GREEN
COM STAT= GREEN or OFF (depends if the
module is communicating with PROFIBUS
slaves)
DBASE STAT= GREEN
TKN HLD= GREEN
OK = GREEN
BP ACT = AMBER
APP STATUS= AMBER
MSTR STAT= GREEN (1sec) /RED (2 secs)
COM STAT= OFF
DBASE STAT= GREEN
TKN HLD= GREEN
OK = GREEN
BP ACT = OFF
APP STATUS= AMBER
4.2.5 Flex Mode (Use Legacy Mode=No)
Debug Access After Power Up
LED Behavior After Power Up
- Module located in slot that is not
configured
OR
- No processor
OR
- Neither sample logics loaded to
processor (LEGACY or FLEX)
No
(Waiting for connection to
processor)
MSTR STAT= OFF
COM STAT=OFF
DBASE STAT=GREEN
TKN HLD= OFF
OK = RED
BP ACT = AMBER
APP STATUS= AMBER
MSTR STAT= RED
COM STAT= OFF
DBASE STAT= GREEN
TKN HLD= GREEN
OK = GREEN
BP ACT = OFF
APP STATUS= AMBER
MSTR STAT= GREEN
COM STAT= GREEN or OFF (depends if
the module is communicating with
PROFIBUS slaves)
DBASE STAT= GREEN
TKN HLD= GREEN
OK = GREEN
BP ACT = AMBER
APP STATUS= OFF