MVI56-PDPMV1 ControlLogix Platform Reference
PROFIBUS DPV1 Master User Manual
Page 201 of 251 ProSoft Technology, Inc.
5.2.3 Master/Slave Communication Phases
The communication between the Master and the slaves takes place in the
following phases:
Parameterization and configuration phase
Usable data transfer phase
Before a DP slave can be integrated into the usable data transfer phase, the
parameterization and configuration phase runs a device identification test that
verifies that the planned configuration matches the actual device configuration for
each slave in the PROFIBUS network. The test verifies that:
The device is actually there
It is the right type of device
The station address set on the device matches the station address in the bus
configuration
The formats, telegram length information, and bus parameters are correct
and
The number of configured inputs and outputs is correct
5.2.4 How Cable Length Affects Communication Rate
Max Bus Cable Length Per Segment
Baud Rates (for 12 Mbps cable)
1.2 km
9.6 kbit/sec
1.2 km
19.2 kbit/sec
1.2 km
93.75 kbit/sec
1.0 km
187.5 kbit/sec
0.5 km
500 kbit/sec
0.2 km
1.5 Mbit/sec
0.1 km
3 Mbit/sec
0.1 km
8 Mbit/sec
0.1 km
12 Mbit/sec