Normal Backplane Operation
The MVI56-PDPMV1 module’s application code initiates the data transfers at the
end of every ControlLogix PLC ladder scan. As such, the MVI56-PDPMV1
module is able to actively read and write the PROFIBUS Cyclic Input/Output data
blocks in the appropriate locations.
Input Data Block (Block ID = 1 to 4)
This block contains the previous input data received from the slaves.
Input Data Block Format (Input Image) (Local:1:I.Data Controller Tag)
You can find the contents of the Input Data Block (Input Image) in the
Local:1:I.Data user controller tags in RSLogix.
Data received from the PROFIBUS slave devices on the
network.
Total size of the PROFIBUS Input Data block is a function of the
PROFIBUS network configuration.
Block ID 1 = Slave bytes 0 to 399
Block ID 2 = Slave bytes 400 to 799
Block ID 3 = Slave bytes 800 to 1199
Block ID 4 = Slave bytes 1200 to 1535
Last out mailbox
message ID processed
from output image
The module confirms the receipt of a mailbox by copying its ID
code (Message ID) to this register.
Current in mailbox
control index
Incremented after the module has transferred a new mailbox
response to the processor.
Current alarm control
index
Incremented after the module has transferred a new alarm to
the processor.
CRC32 checksum for PROFIBUS Master configuration
downloaded from configuration utility
MVI56-PDPMV1 module configuration checksum for module
configuration downloaded from configuration utility
Write block ID of Output image to receive (1 to 4 for data, 0 or -1
if no data)
Read Block ID number -1 to 4