MVI69E-MBS CompactLogix Platform Using Controller Tags
Modbus Serial Enhanced Communication Module User Manual
ProSoft Technology, Inc. Page 83 of 154
June 28, 2017
MBS.CONTROL.SlavePoll
This array allows the processor to enable, disable and retrieve status for slaves.
Tag Name
Range
Description
MBS.CONTROL.SlavePoll.Portx
-
Port x slave polling control
MBS.CONTROL.SlavePoll.Portx.
EnableSlaves
0 or 1
Slave Poll request
0 = Disable, 1 = Enable
MBS.CONTROL.SlavePoll.Portx.
EnableSlaveCount
1 to 60
Number of slaves to be enabled
MBS.CONTROL.SlavePoll.Portx.
EnableSlavesIDs[x]
-
Data array associated to enable slave request
where word x corresponds to slave ID x (0-based).
1 = Enable slave
MBS.CONTROL.SlavePoll.Portx.
DisableSlaves
0 or 1
Triggers disable slaves request
0 = Disable, 1 = Enable
MBS.CONTROL.SlavePoll.Portx.
DisableSlaveCount
1 to 60
Number of slaves to be disabled
MBS.CONTROL.SlavePoll.Portx.
DisableSlavesIDs[x]
-
Data array associated to disable slave request
where word x corresponds to slave ID x (0-based).
1 = Disable slave
MBS.CONTROL.SlavePoll.Portx.
GetSlavesStatus
0 or 1
Triggers request to read slave status
0 = Disable, 1 = Enabled
MBS.CONTROL.SlavePoll.Portx.
SlavesStatus[x]
-
Data array with status
MBS.CONTROL.Time
This array allows the processor to get or set module time.
Tag Name
Range
Description
SetTime
0 or 1
Sends the PLC time to the module
0 = Disable, 1 = Enable
GetTime
0 or 1
Retrieves the time from the module to PLC
0 = Disable, 1 = Enable
Year
0 to 9999
Four digit year value. Example: 2015
Month
1 to 12
Month
Day
1 to 31
Day
Hour
0 to 23
Hour
Minute
0 to 59
Minute
Second
0 to 59
Second
Milliseconds
0 to 999
Millisecond