EasyManua.ls Logo

Rockwell Automation Allen-Bradley 1769-L24ER-QBFC1B

Rockwell Automation Allen-Bradley 1769-L24ER-QBFC1B
332 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 1769-UM021I-EN-P - May 2018 195
Use I/O Modules with CompactLogix 5370 L2 Controllers Chapter 8
4. Repeat step 3 for all embedded I/O wires that are needed in your
application.
To remove a wire from the removable connector, complete these steps.
1. Verify that the control system is not powered.
2. Use a small screwdriver to push the spring release clip and pull out the
wire.
You can use a continuity tester to determine if the connection point is
operating correctly, that is, the connection point is a complete circuit. You use a
continuity tester if any issues arise with a removable connector and you suspect
that a connection point can no longer be functioning as a complete circuit.
The indication mechanism, for example, a light that illuminates on the tester,
varies by continuity tester. The following example graphic shows a continuity
tester with one connection point. In this case, if the circuit is operating
correctly, the indicator light turns on.
Insert a continuity tester into the suspected I/O connection point as shown in
the following graphic.
Continuity Tester
Small hole on
opposite from
termination point
in removable
connector.

Table of Contents

Related product manuals