EasyManuals Logo

Rockwell Automation Allen-Bradley 1769-L24ER-QBFC1B User Manual

Rockwell Automation Allen-Bradley 1769-L24ER-QBFC1B
332 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #242 background imageLoading...
Page #242 background image
242 Rockwell Automation Publication 1769-UM021I-EN-P - May 2018
Chapter 9 Use I/O Modules with CompactLogix 5370 L3 Controllers
Module Fault Related to RPI Estimates
When following the guidelines described in Table 29 , most CompactLogix
5370 L3 control systems operate as expected. Some systems that follow the
guidelines can experience a Module RPI Overlap minor fault as described in
the following table.
Name Fault
Information
Condition In Which Fault Occurs
Module
RPI
Overlap
(Type 03) I/O fault
(Code 94) Module
RPI overlap
detected
Module Slot = x,
where x is the slot
number of the I/O
module in the I/O
Configuration
section
This fault is logged when the current RPI update of an I/O module overlaps with
its previous RPI update. The Minor Faults tab in the Controller Properties dialog
box indicates in which module the RPI overlap occurs.
If multiple I/O modules experience the fault, the application indicates that the
fault occurred on the first such I/O module. Typically, it is an I/O module with a
large Input/Output array sizes. Example modules that use large Input/Output
array sizes include the 1769-SDN and 1769-HSC modules. In these cases, we
recommend that you adjust the RPI of the module to eliminate the fault.
Once the fault is cleared from the first I/O module, the application indicates the
next module that experiences the fault. This pattern continues until the fault is
cleared from all affected I/O modules.
To avoid this fault, set the RPI rate of the I/O modules to higher numerical values.
We recommend that you use an RPI value that is not a common multiple of other
module RPI values, such as 2.5 ms, 5.5 ms, or 7 ms.
• We recommend that you do not run CompactLogix 5370 L3 control systems
with Module RPI Overlap faults.
• A system that experiences many Module RPI Overlap faults cannot operate
optimally because I/O data is not sampled at the expected rate that the RPI
settings determine.
• When the project is downloaded or the RPI value of an I/O module is
adjusted, it is expected to have a minor fault. Faults under these conditions
are transitionary. Clear the fault and wait for the fault to reappear before
adjusting the RPI value or the task priorities.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen-Bradley 1769-L24ER-QBFC1B and is the answer not in the manual?

Rockwell Automation Allen-Bradley 1769-L24ER-QBFC1B Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen-Bradley 1769-L24ER-QBFC1B
CategoryController
LanguageEnglish

Related product manuals