80 Rockwell Automation Publication 520-UM001K-EN-E - August 2021
Chapter 3 Programming and Parameters
Basic Display Group (continued)
b020 [Average Power] Related Parameter(s): A555
Average power used by the motor since the last reset of the meters.
Values
Default: Read Only
Min/Max: 0.00/(Drive Rated Power x 2)
Display: 0.01 kW
b021 [Elapsed kWh] Related Parameter(s): b022
Accumulated output energy of the drive. When the maximum value of this parameter is reached, it resets to zero and b022 [Elapsed MWh] is incremented.
Values
Default: Read Only
Min/Max: 0.0/100.0 kWh
Display: 0.1 kWh
b022 [Elapsed MWh] Related Parameter(s): b021
Accumulated output energy of the drive.
Values
Default: Read Only
Min/Max: 0.0/6553.5 MWh
Display: 0.1 MWh
b023 [Energy Saved] Related Parameter(s): A555
Total energy savings of using this drive compared to an across the line starter since the last reset of the meters.
Values
Default: Read Only
Min/Max: 0.0/6553.5 kWh
Display: 0.1 kWh
b024 [Accum kWh Sav] Related Parameter(s): b025
Total approximate accumulated energy savings of the drive compared to using an across the line starter.
Values
Default: Read Only
Min/Max: 0.0/6553.5 kWh
Display: 0.1 = 10 kWh
b025 [Accum Cost Sav] Related Parameter(s): b024, P052, A555
Total approximate accumulated cost savings of the drive compared to using an across the line starter.
[Accum Cost Sav] = [Average kWh cost] x [Accum kWh Sav]
Values
Default: Read Only
Min/Max: 0.0/6553.5
Display: 0.1
b026 [Accum CO2 Sav] Related Parameter(s): A555
Total approximate accumulated CO2 savings of the drive compared to using an across the line starter.
Values
Default: Read Only
Min/Max: 0.0/6553.5 kg
Display: 0.1 kg