144 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Chapter 6 Logging
Data Log Results Files
The PowerMonitor 5000 unit stores the data log in multiple comma-separated-
value (.csv) files, and selects a file duration that is based on the value of the
Data_Logging_Interval parameter.
In addition, the active data log file is closed and a new file is created when any of
the following events occur:
Initial powerup of the power monitor
Subsequent powerup, if the active data log file is older than the expected
duration
If the Data_Logging_Interval or any other data log parameter is changed
The Data_Log_Mode parameter determines what happens when the log contains
60,000 records:
If set to 0 = Fill and stop recording when log is full, no new data log files
are created and no more data is logged.
If set to 1 = Overwrite when log is full starting with the earliest record, a
new file is created and data logging continues uninterrupted. This value is
the default setting.
File Names
Data log file names have the following semantics:
DataLog_YYYYMMDD_hhmm_HH.csv, where:
YYYYMMDD_hhmm - the file creation date and time
HH - UTC hour avoids duplication during daylight-saving time transition
Interval, Seconds Log File Duration File End Date Maximum Records
1~30 Hour New hour, xx:00:00
(hh:mm:ss)
3600
31~90 Day New day, 00:00:00
(hh:mm:ss)
2788
>90 Week Sunday of a week,
00:00:00 (hh:mm:ss)
6646