IEEE 519 Pass/Fail and TDD Appendix F
These bitfields reports the short-term or long-term status of harmonics of order
2
17.
0 = PASS
1 = FAIL
Bit0 - 2nd_Harmonic_PASS_FAIL
Bit1 - 3rd_Harmonic_PASS_FAIL
•…
Bit15 - 17th_Harmonic_PASS_FAIL
ShortTerm_18th_To_33rd_Harmonic_Status
LongTerm_18th_To_33rd_Harmonic_Status
These bitfields reports the short-term or long-term status of harmonics of order
18
33.
0 = PASS
1 = FAIL
Bit0 - 18th_Harmonic_PASS_FAIL
Bit1 - 19th_Harmonic_PASS_FAIL
•…
Bit15 - 33rd_Harmonic_PASS_FAIL
ShortTerm_34th_To_40th_Harmonic_Status
LongTerm_34th_To_40th_Harmonic_Status
These bitfields reports the short-term or long-term status of harmonics of order
34…40.
0 = PASS
1 = FAIL
Bit0 - 34th_Harmonic_PASS_FAIL
Bit1 - 35th_Harmonic_PASS_FAIL
•…
Bit6 - 40th_Harmonic_PASS_FAIL
Bit 7 … Bit 15 - Reserved, always = 0
IEEE 519 Short-Term and
Long-Term Harmonic
Results
The six data tables that are listed, provide an indication of individual current
harmonic distortion and TDD (Total Demand Distortion). If you have selected
voltage as the output parameter the tables list voltage distortions and THD
(Total Harmonic Distortion).
PowerQuality.IEEE519_CH1_ShortTerm_Results
PowerQuality.IEEE519_CH2_ShortTerm_Results
PowerQuality.IEEE519_CH3_ShortTerm_Results
PowerQuality.IEEE519_CH1_LongTerm_Results
PowerQuality.IEEE519_CH2_LongTerm_Results
PowerQuality.IEEE519_CH3_LongTerm_Results