Rockwell Automation Publication 1426-UM001J-EN-P - August 2019 461
IEEE 519 Pass/Fail and TDD Appendix F
These bitfields reports the short-term or long-term status of harmonics of order
2
…17.
0 = PASS
1 = FAIL
• Bit0 - 2nd_Harmonic_PASS_FAIL
• Bit1 - 3rd_Harmonic_PASS_FAIL
•…
• Bit15 - 17th_Harmonic_PASS_FAIL
• ShortTerm_18th_To_33rd_Harmonic_Status
• LongTerm_18th_To_33rd_Harmonic_Status
These bitfields reports the short-term or long-term status of harmonics of order
18
…33.
0 = PASS
1 = FAIL
• Bit0 - 18th_Harmonic_PASS_FAIL
• Bit1 - 19th_Harmonic_PASS_FAIL
•…
• Bit15 - 33rd_Harmonic_PASS_FAIL
• ShortTerm_34th_To_40th_Harmonic_Status
• LongTerm_34th_To_40th_Harmonic_Status
These bitfields reports the short-term or long-term status of harmonics of order
34…40.
0 = PASS
1 = FAIL
• Bit0 - 34th_Harmonic_PASS_FAIL
• Bit1 - 35th_Harmonic_PASS_FAIL
•…
• Bit6 - 40th_Harmonic_PASS_FAIL
• Bit 7 … Bit 15 - Reserved, always = 0
IEEE 519 Short-Term and
Long-Term Harmonic
Results
The six data tables that are listed, provide an indication of individual current
harmonic distortion and TDD (Total Demand Distortion). If you have selected
voltage as the output parameter the tables list voltage distortions and THD
(Total Harmonic Distortion).
• PowerQuality.IEEE519_CH1_ShortTerm_Results
• PowerQuality.IEEE519_CH2_ShortTerm_Results
• PowerQuality.IEEE519_CH3_ShortTerm_Results
• PowerQuality.IEEE519_CH1_LongTerm_Results
• PowerQuality.IEEE519_CH2_LongTerm_Results
• PowerQuality.IEEE519_CH3_LongTerm_Results