Rockwell Automation Publication 1426-UM001J-EN-P - August 2019 187
Logic Functions Chapter 7
Command Word One
Set this command word value to execute the corresponding action. These values
are the selections:
10 = Force KYZ Output On
11 = Force KYZ Output Off
12 = Remove Force from KYZ
13 = Force Relay 1 Output On
14 = Force Relay 1 Output Off
15 = Remove Force from Relay 1
16 = Force Relay 2 Output On
17 = Force Relay 2 Output Off
18 = Remove Force from Relay 2
19 = Force Relay 3 Output On
20 = Force Relay 3 Output Off
21 = Remove Force from Relay 3
Related Functions
Configuration lock
•Status Log
•Setpoints
•EDS add-on profile
Status Inputs
The PowerMonitor 5000 unit has four self-powered (24V DC) status inputs.
Two typical uses for status inputs are to totalize external pulse meters and to
synchronize the demand end of interval (EOI).
Applications
These inputs apply to all models.
Operation
Each time status input 1 sees an off to on transition, the status input 1 scale factor
is added to the status input 1 count. The count continues to increase, rolling over
to zero at a value of 9,999,999,999,999 (10
13
– 1). Status inputs 2, 3, and 4
operate in the same fashion. The status input 2 counter operates whether or not
the input is used for demand EOI synchronization.