474 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Appendix H EN 50160 Conformance Tracking
Operation
This section describes how the power monitor measures EN 50160 conformance.
Power Frequency
The mean fundamental frequency is measured in each valid 10 second interval.
The following are the conforming ranges for these measurements in low- and
medium-voltage systems:
Synchronously Connected
Range 1: 50 Hz ± 1% during 99.5% of a year
Range 2: 50 Hz + 4% / - 6% during 100% of the time
Not Synchronously Connected
Range 1: 50 Hz ± 2% during 95% of each week
Range 2: 50 Hz ± 15% during 100% of the time
Supply Voltage Variations (low-voltage systems)
The mean rms supply voltage is measured in each valid 10 minute interval. The
following are the confirming ranges for these measurements in low-voltage
systems:
Synchronously Connected
Range 1: within ± 10% of nominal during 95% of each week
Range 2: within + 10% / - 15% of nominal during 100% of the time
Not Synchronously Connected
Within + 10% / - 15% of nominal during 100% of the time
Supply Voltage Variations (medium-voltage systems)
The following are the conforming ranges for these measurements in medium-
voltage systems:
Synchronously Connected
Range 1: within ± 10% of nominal during 99% of each week
Range 2: within + 15% / - 15% of nominal during 100% of the time
Not Synchronously Connected
Within + 10% / - 15% of nominal during 100% of the time