Rockwell Automation Publication 1426-UM001J-EN-P - August 2019 81
Metering Chapter 4
Energy Metering
The power monitor meters the following energy consumption parameters:
• Real Energy Consumption (kWh, GWH), Forward, Reverse, Net
• Reactive Energy Consumption (kVARh, GVARh) Forward, Reverse, Net
• Apparent Energy Consumption (kVAh, GVAh) Net
• Current Consumption (Amp-h)
Applications
This function applies to all PowerMonitor 5000 models.
Table 8 - Energy Metering Metered Parameters
Parameter Description Range Units
GWh_Fwd Total real energy consumed 0…9,999,999 GWh
kWh_Fwd Total real energy consumed 0.000…999,999 kWh
GWh_Rev Total real energy produced 0…9,999,999 GWh
kWh_Rev Total real energy produced 0.000…999,999 kWh
GWh_Net The sum of forward and reverse real energy ± 0…9,999,999 GWh
kWh_Net The sum of forward and reverse real energy ± 0.000…999,999 kWh
GVARh_Fwd Total reactive energy consumed 0…9,999,999 GVARh
kVARh_Fwd Total reactive energy consumed 0.000…999,999 kVARh
GVARh_Rev Total reactive energy produced 0…9,999,999 GVARh
kVARh_Rev Total reactive energy produced 0.000…999,999 kVARh
GVARh_Net Total sum of forward and reverse reactive energy ±0…9,999,999 GVARh
kVARh_Net Total sum of forward and reverse reactive energy ±0.000…999,999 kVARh
GVAh Total apparent energy consumed 0…9,999,999 GVAh
kVAh Total apparent energy consumed 0.000…999,999 kVAh
GAh Accumulated amp-hours consumed 0…9,999,999 GAh
kAh Accumulated amp-hours consumed 0.000…999,999 kAh