148 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Chapter 6 Logging
Min/Max Log
The PowerMonitor 5000 unit records time-stamped minimum and maximum
values for all real-time metering data (except for energy data).
Min/Max Log Results
Min/max log records can be retrieved from the PowerMonitor 5000 web page or
FTP server. The power monitor generates the log file at the time of the request.
Records can also be retrieved individually or sequentially by using the data table
interface.
File Name
The min/max log is named Min_Max_Log.csv.
Logged Parameters
The first record in the min/max log file is a header listing the attribute names for
each logged parameter.
Table 18 - Min/Max Log Logged Parameters
Attribute Name Description
MinMax_Parameter_Number The number of the parameter from the MIN_MAX parameter list.
MIN_Value The minimum value that is recorded since the last MIN_MIX clear.
MAX_Value The maximum value that is recorded since the last MIN_MIX clear.
Timestamp_MIN_Year The year at which this MIN record was logged.
Timestamp_MIN_Mth_Day The month and day this MIN record was logged.
Timestamp_MIN_Hr_Min The hour and minute this MIN record was logged.
Timestamp_MIN_Sec_ms The seconds and milliseconds this MIN record was logged.
Timestamp_MAX_Year The year at which this MAX record was logged.
Timestamp_MAX_Mth_Day The month and day this MAX record was logged.
Timestamp_MAX_Hr_Min The hour and minute this MAX record was logged.
Timestamp_MAX_Sec_ms The seconds and milliseconds this MAX record was logged.