Rockwell Automation Publication 1426-UM001J-EN-P - August 2019 221
Communication Chapter 9
Optional DeviceNet
Communication
PowerMonitor 5000 units can be optionally equipped with a DeviceNet®
communication port. A DeviceNet communication port can be factory installed
or field installed by you. The DeviceNet network is an open-standard, multi-
vendor, industrial device data network that uses various physical media. The
DeviceNet network also provides 24V DC power to devices connected to the
network. The DeviceNet network port and the native Ethernet network port can
be used simultaneously.
Setup
Setup parameters for the optional DeviceNet port are found in the
Configuration.OptionalComm.DNT
table on page 329.
Mac ID
Selects the DeviceNet node address. The range is 0…63 (default).
Communication Rate
Selects the DeviceNet network communication (data) rate, and must be selected
to match the remaining devices on the network. The selections are the following:
• 0 = 125 Kbps
• 1 = 250 Kbps
• 2 = 500 Kbps
•3 = Autobaud
Optional ControlNet
Communication
PowerMonitor 5000 units can be optionally equipped with a ControlNet®
communication port. A ControlNet communication port can be factory
installed or field installed by you. The ControlNet network is an open-standard,
multi-vendor, industrial device data network that supports scheduled, I/O
communication and unscheduled messaging. The ControlNet port and the
native Ethernet port can be used simultaneously.
Setup
The Configuration.OptionalComm.CNT table, on page 330, contains the
Address tag, the only set up parameter. Valid ControlNet addresses range from
1…99. The default value is 255.