Rockwell Automation Publication 1426-UM001J-EN-P - August 2019 329
PowerMonitor 5000 Unit Data Tables Appendix A
Configuration.OptionalComm.DNT
Table 80 - Table Properties
CIP Instance Number 816
PCCC File Number N25
No. of Elements 30
Length in Words 30
Data Type Int16
Data Access Read/Write
Table 81 - Configuration.OptionalComm.DNT Data Table
Element Number Type Tag Name Description Default Range
0 Int16 DeviceNet_Address DeviceNet® optional card device address 63 0…63
1 Int16 DeviceNet_Baudrate DeviceNet optional card communication rate.
0 - 125k
1 - 250k
2 - 500k
3 - AutoBaud
30…3
2…29 Int16 Reserved Future Use 0 0