Rockwell Automation Publication 1426-UM001J-EN-P - August 2019 87
Metering Chapter 4
Power Metering
This function applies to all PowerMonitor 5000 models.
Only total three-phase power results are provided when Direct Delta or Open
Delta wiring modes are selected.
Table 10 - Power Metering Metered Parameters
Parameter Description Range Units
L1_kW Power of individual phase or sum of phases; signed to show direction -9.999E15…9.999E15 kW
L2_kW
L3_kW
Total_ kW
L1_kVAR Reactive power of individual phase or sum of all phases; signed to show direction -9.999E15…9.999E15 kVAR
L2_kVAR
L3_kVAR
Total_kVAR
L1_kVA Apparent power of individual phase or sum of all phases 0…9.999E15 kVA
L2_kVA
L3_kVA
Total_ kVA
L1_True_PF_% The ratio between power and apparent power for individual phase or all phases 0.00…100.00 %
L2_True_PF_%
L3_True_PF_%
Avg_True_PF
L1_Disp_PF The cosine of the phase angle between the fundamental voltage and current for an individual
phase or all phases
0.00…100.00 %
L2_Disp_PF
L3_Disp_PF
Avg_Disp_PF
L1_PF_Lead_Lag_Indicator Lead or lag indicator for power factor
1 = leading
-1 = lagging
-1…+1 -
L2_PF_Lead_Lag_Indicator
L3_PF_Lead_Lag_Indicator
Total_PF_Lead_Lag_Indicator