86 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Chapter 4 Metering
Number_Demand_Periods
Specifies the number of demand periods to average for demand measurement.
These values are for this parameter:
1 = Used for fixed demand period
2…15 = Used for sliding window demand period
Forced_Demand_Sync_Delay
When configured for an external demand source, this parameter defines how
long the unit waits for the expected control input (for example, EOI pulse or
network demand broadcast), before the unit starts a new demand period. If this
delay occurs, an entry is made in the Event Log. These values are for this
parameter:
0 = Wait forever
1…900 = Wait this many seconds before starting a new demand period
Network demand synchronization is available on units that are connected to an
Ethernet network. Network-demand synchronization parameters are found in
the Communications_Native tab under Configuration tab.
Demand_Broadcast_Mode_Select
Demand Ethernet broadcast selection. These values are for this parameter:
0 = Slave (default)
1 = Master
Demand_Broadcast_Port
The common port for demand broadcast messages. These values are for this
parameter:
300 (default)…400
Commands
Controller command (EOI signal)
Related Functions
• Status inputs
• Time of use log
• Configuration lock
IMPORTANT There must be only one master per demand network.