328 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Appendix A PowerMonitor 5000 Unit Data Tables
23 Real IEEE1159_Voltage_Imbalance_Limit_% The percent of voltage Imbalance to create an imbalance event 3 1.00…10.00
24 Real IEEE1159_Current_Imbalance_Limit_% The percent of current Imbalance to create an imbalance event 25 1.00…50.00
25 Real IEEE1159_DCOffset_Harmonic_Avg_Intvl_m The rolling average interval for DC offset and Harmonics in 
minutes
5 1…15
26 Real IEEE1159_Voltage_DCOffset_Limit_% The percent of DC offset limitation  0.1 0.00…1.00
27 Real IEEE1159_Voltage_THD_Limit_% The percent of voltage THD limitation 5 0.00…20.00
28 Real IEEE1159_Current_THD_Limit_% The percent of current THD limitation 10 0.00…20.00
29 Real IEEE1159_PowerFrequency_Avg_Intvl_s The rolling average interval for power frequency in seconds. 1 1…10
30 Real IEEE1159_PowerFrequency_Limit_Hz The limitation on power frequency variation in Hz. 0.1 0.1…0.2
31 Real IEEE1159_PowerFrequency_Hysteresis_Hz Hysteresis of power frequency  0.02 0.01…0.05
32 Real IEEE519_Compliance_Parameter IEEE 519 Compliance Parameter 
0 = Current 
1=  Voltage
00…1
33 Real IEEE519_MAX_Isc_Amps Short circuit current available at the point of common coupling. 
(PCC)  IMPORTANT: When Isc is ‘0’ or IL is ‘0’, the first row in IEEE 
519 Current Distortion Limits table is selected for compliance.
0 0.00…1,000,000.00
34 Real IEEE 519 MAX_IL_Amps Average maximum demand for current for the preceding 12 
months. IMPORTANT: When IL is ‘0’ the current THD instead of TDD 
is used for compliance.
0 0.00…1,000,000.00
35 Real IEEE1159_Voltage_TID_Limit_% The percent of Voltage TID limitation 5 0.00…20.00 
(M8_Only)
36 Real IEEE1159_Current_TID_Limit_% The percent of Current TID limitation 10 0.00…20.00 
(M8_Only)
37 Real IEEE1159_Short_Term_Perceptability_Limit_
P
st
The P
st
 limit configuration for Voltage Fluctuations 1 0.2…4.0 (M8_Only)
38 Real Metering_Snapshot_Parameter_Selection This option configures what set of parameters is used when the 
metering snapshot command is issued: 
0 = Single cycle parameters
1 = Harmonics voltage and current HDS and IHDS parameters
2 = 5 Hz harmonic results through the 50th harmonic
0 0…2 (M8_Only)
39 Real Transient_Detection_Threshold_% The threshold setting for the percent of transient detection.  
0% = disable function
0.1…50% sets the threshold for transient recording.
4 0.0…50.0 
(M8_Only)
40 Real Mains_Signaling_Frequency_Hz The monitoring frequency of the control signal in Hz 500 5…3000 (M8_Only)
41 Real Mains_Signaling_Recording_Length The maximum recording length in seconds. 120 1…120 (M8_Only)
42 Real Mains_Signaling_Threshold_% The threshold in percent of signal level to the mains voltage.  A 
value of 0% disables the mains signal recording.
0 0…15 (M8_Only)
43 Real Under_Over_Voltage_Deviation_Threshold_
%
The percent under voltage or overvoltage of the mains connection 
to start recording deviation.  
0% disables.
5 0…15 (M8_Only)
44 Real PowerFrequency_Synchronization Sets the environment of the metering system.  
0 = Synchronous connection to an interconnected system
1 = Not synchronous to an interconnected system.  (Islanded).
0 0…1 (M8_Only)
45…49 Real Reserved Reserved for future use. 0 0
Table 79 - Configuration.PowerQuality Data Table (continued)
Element 
Number
Type Tag Name Description Default Range