186 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Chapter 7 Logic Functions
Semantics of selections:
• Last-state = hold the output in its last state on communication loss
• De-energize = put output into de-energized or normal state on 
communication loss 
• Resume = restore output control when communication recovers
• Freeze = maintain state of output when communication recovers until one 
of the following occurs:
– Logic controller enters program mode
– Power cycle to the power monitor
– Change the parameter value to ‘resume’ 
• Local Control = Revert to local power monitor control (pulsed or 
setpoint) on communication loss. When communication recovers and 
connection is re-established, output control by the connection host 
resumes.
Status
Relay and KYZ output status is reported by the state of the following Boolean 
tags, found in the Status.DiscreteIO
 table on page 342. 
For each tag, 0 = False, 1 = True.
KYZ _Output_Energized
KYZ_Forced_On
KYZ_Forced_Off
Relay_1_Output_Energized
Relay_1_Forced_On
Relay_1_Forced_Off
Relay_2_Output_Energized
Relay_2_Forced_On
Relay_2_Forced_Off
Relay_3_Output_Energized
Relay_3_Forced_On
Relay_3_Forced_Off
Commands
The following command parameters are found in the 
Command.System_Registers
 table on page 368. These commands are not 
permitted if an Exclusive Owner connection has been established with a Logix 
controller.