Logic Functions Chapter 7
KYZ_Solid_State_Output_Scale
Output_Relay_1_Output_Scale
Output_Relay_2_Output_Scale
Output_Relay_3_Output_Scale
The output parameter that is divided by the scale is the output pulse rate.
Example: Wh is selected for the parameter and 1000 is the scale value. The
output is pulsed every 1000 Wh, or 1 kWh. This parameter is ignored for
setpoint or communication operation.
KYZ_Pulse_Duration_Setting
Output_Relay_1_Pulse_Duration_Setting
Output_Relay_2_Pulse_Duration_Setting
Output_Relay_3_Pulse_Duration_Setting
Defines the duration of each output pulse. These values are the choices:
0 = KYZ-style transition output (toggle)
50…1000 = Pulse duration in milliseconds, rounded to the nearest 10 ms.
This parameter is ignored for setpoint or communication operation.
Default_KYZ_State_On_Comm_Loss
Default_Relay_1_State_On_Comm_Loss
Default_Relay_2_State_On_Comm_Loss
Default_Relay_3_State_On_Comm_Loss
In Class 1 scheduled communication operation, this parameter defines the
behavior of the specified output if the power monitor experiences a
communication loss/communication recovery. These values are the selections:
0 = Last state/resume
1 = Last state/freeze
2 = De-energize/resume
3 = De-energize/freeze
4 = Local control