342 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Appendix A PowerMonitor 5000 Unit Data Tables
Status.DiscreteIO
Table 108 - Table Properties
CIP Instance Number 826
PCCC File Number N35
No. of Elements 112
Length in Words 112
Data Type Int16
Data Access Read Only
Table 109 - Status.DiscreteIO Data Table
Element
Number
Type Tag Name Description Range
0 Int16 Status_Input_States Indicates the overall Status Input Condition 65,535
Bit 0 Status_Input_1_Actuated Indicates Status 1 actuated 0 or 1
Bit 1 Status_Input_2_Actuated Indicates Status 2 actuated 0 or 1
Bit 2 Status_Input_3_Actuated Indicates Status 3 actuated 0 or 1
Bit 3 Status_Input_4_Actuated Indicates Status 4 actuated 0 or 1
Bit 4 KYZ _Output_Energized Indicates Output KYZ Energized 0 or 1
Bit 5 KYZ_Forced_On Software Control Forced On KYZ 0 or 1
Bit 6 KYZ_Forced_Off Software Control Forced Off KYZ 0 or 1
Bit 7 Relay_1_Output_Energized Indicates Output Relay 1 Energized 0 or 1
Bit 8 Relay_1_Forced_On Software Control Forced On Relay 1 0 or 1
Bit 9 Relay_1_Forced_Off Software Control Forced Off Relay 1 0 or 1
Bit 10 Relay_2_Output_Energized Indicates Output Relay 2 Energized 0 or 1
Bit 11 Relay_2_Forced_On Software Control Forced On Relay 2 0 or 1
Bit 12 Relay_2_Forced_Off Software Control Forced Off Relay 2 0 or 1
Bit 13 Relay_3_Output_Energized Indicates Output Relay 3 Energized 0 or 1
Bit 14 Relay_3_Forced_On Software Control Forced On Relay 3 0 or 1
Bit 15 Relay_3_Forced_Off Software Control Forced Off Relay 3 0 or 1
1…111 Int16 Reserved Future Use 0