Rockwell Automation Publication 1426-UM001J-EN-P - August 2019 343
PowerMonitor 5000 Unit Data Tables Appendix A
Status.Wiring_Diagnostics
Table 110 - Table Properties
CIP Instance Number 829
PCCC File Number F38
No. of Elements 33
Length in Words 66
Data Type Real
Data Access Read Only
Table 111 - Status.Wiring_Diagnostics Data Table
Element
Number
Type Tag Name Description Range
0 Real Command_Status This is the wiring diagnostics command status.
0 = Command Active
1 = Input Level Low
2 = Disabled
3 = Waiting Command
0…3
1 Real Voltage_Input_Missing Reports on all three phases.
-1 = Test not run
0 = Test passed
1 = Phase 1 missing
2 = Phase 2 missing
3 = Phase 3 missing
12 = Phase 1 and 2 missing
13 = Phase 1 and 3 missing
23 = Phase 2 and 3 missing
123 = All phases missing
-1…123
2 Real Current_Input_Missing Reports on all three phases.
-1 = Test not run
0 = Test passed
1 = Phase 1 missing
2 = Phase 2 missing
3 = Phase 3 missing
12 = Phase 1 and 2 missing
13 = Phase 1 and 3 missing
23 = Phase 2 and 3 missing
123 = All phases missing
-1…123
3 Real Range1_L97_C89_Status This is the pass fail status for Range 1 diagnostics.
0 = Pass
1 = Failed
0 or 1
4 Real Range1_Voltage_Input_Inverted Reports on all three phases.
-1 = Test not run
0 = Test passed
1 = Phase 1 inverted
2 = Phase 2 inverted
3 = Phase 3 inverted
12 = Phase 1 and 2 inverted
13 = Phase 1 and 3 inverted
23 = Phase 2 and 3 inverted
123 = All phases inverted
-1…123