344 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Appendix A PowerMonitor 5000 Unit Data Tables
5 Real Range1_Current_Input_Inverted Reports on all three phases.
-1 = Test not run
0 = Test passed
1 = Phase 1 inverted
2 = Phase 2 inverted
3 = Phase 3 inverted
12 = Phase 1 and 2 inverted
13 = Phase 1 and 3 inverted
23 = Phase 2 and 3 inverted
123 = All phases inverted
-1…123
6 Real Range1_Voltage_Rotation Reports on all three phases. The reported sequence represents each phase.
1…321 designating phase and rotation. 
Example: 123 = Phase 1 then phase 2 then phase 3  
-1 = Test not run 
4 = Invalid Rotation 
5 = Out of range 
-1…132
7 Real Range1_Current_Rotation Reports on all three phases.  The reported sequence represents each phase.
1…321 designating phase and rotation. 
Example: 123 = Phase 1 then phase 2 then phase 3  
-1 = Test not run  
4 = Invalid Rotation  
5 = Out of range 
-1…321
8 Real Range2_L85_C98_Status This is the pass fail status for Range 2 diagnostics.
0 = Pass
1 = Failed
0 or 1
9 Real Range2_Voltage_Input_Inverted Reports on all three phases.
-1 = Test not run
0 = Test passed
1 = Phase 1 inverted
2 = Phase 2 inverted
3 = Phase 3 inverted
12 = Phase 1 and 2 inverted
13 = Phase 1 and 3 inverted
23 = Phase 2 and 3 inverted
123 = All phases inverted
-1…123
10 Real Range2_Current_Input_Inverted Reports on all three phases.
-1 = Test not run
0 = Test passed
1 = Phase 1 inverted
2 = Phase 2 inverted
3 = Phase 3 inverted
12 = Phase 1 and 2 inverted
13 = Phase 1 and 3 inverted
23 = Phase 2 and 3 inverted
123 = All phases inverted
-1…123
11 Real Range2_Voltage_Rotation Reports on all three phases. The reported sequence represents each phase.
1…321 designating phase and rotation. 
Example: 123 = Phase 1 then phase 2 then phase 3 
-1 = Test not run
4 = Invalid Rotation
5 = Out of range 
-1…132
Table 111 - Status.Wiring_Diagnostics Data Table (continued)
Element 
Number
Type Tag Name Description Range