Rockwell Automation Publication 1426-UM001J-EN-P - August 2019 345
PowerMonitor 5000 Unit Data Tables Appendix A
12 Real Range2_Current_Rotation Reports on all three phases. The reported sequence represents each phase.
1…321 designating phase and rotation.
Example: 123 = Phase 1 then phase 2 then phase 3
-1 = Test not run
4 = Invalid Rotation
5 = Out of range
-1…321
13 Real Range3_L52_L95_Status This is the pass fail status for Range 3 diagnostics.
0 = Pass
1 = Failed
0 or 1
14 Real Range3_Voltage_Input_Inverted Reports on all three phases.
-1 = Test not run
0 = Test passed
1 = Phase 1 inverted
2 = Phase 2 inverted
3 = Phase 3 inverted
12 = Phase 1 and 2 inverted
13 = Phase 1 and 3 inverted
23 = Phase 2 and 3 inverted
123 = All phases inverted
-1…123
15 Real Range3_Current_Input_Inverted Reports on all three phases.
-1 = Test not run
0 = Test passed
1 = Phase 1 inverted
2 = Phase 2 inverted
3 = Phase 3 inverted
12 = Phase 1 and 2 inverted
13 = Phase 1 and 3 inverted
23 = Phase 2 and 3 inverted
123 = All phases inverted
-1…123
16 Real Range3_Voltage_Rotation Reports on all three phases. The reported sequence represents each phase.
1…321 designating phase and rotation.
Example: 123 = Phase 1 then phase 2 then phase 3
-1 = Test not run
4 = Invalid Rotation
5 = Out of range
-1…132
17 Real Range3_Current_Rotation Reports on all three phases. The reported sequence represents each phase.
1…321 designating phase and rotation.
Example: 123 = Phase 1 then phase 2 then phase 3
-1 = Test not run
4 = Invalid Rotation
5 = Out of range
-1…321
18 Real Voltage_Phase_1_Angle Shows the present phase angle of this channel. Always 0 degrees for voltage phase 1. 0…359.99
19 Real Voltage_Phase_1_Magnitude Shows the present magnitude of this phase. 0…9,999,999
20 Real Voltage_Phase_2_Angle Shows the present phase angle of this channel. 0…359.99
21 Real Voltage_Phase_2_Magnitude Shows the present magnitude of this phase. 0 …9,999,999
22 Real Voltage_Phase_3_Angle Shows the present phase angle of this channel. 0…359.99
23 Real Voltage_Phase_3_Magnitude Shows the present magnitude of this phase. 0…9,999,999
24 Real Current_Phase_1_Angle Shows the present phase angle of this channel. 0…359.99
25 Real Current_Phase_1_Magnitude Shows the present magnitude of this phase. 0…9,999,999
26 Real Current_Phase_2_Angle Shows the present phase angle of this channel. 0…359.99