368 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Appendix A PowerMonitor 5000 Unit Data Tables
Command.System_Registers
Table 130 - Table Properties
CIP Instance Number 838
PCCC File Number F47
No. of Elements 45
Length in Words 90
Data Type Real
Data Access Write Only
Table 131 - Command.System_Registers Data Table
Element 
Number
Type Tag Name Description Default Range
0 Real Command Word One These commands can be sent to the power monitor. When using the optional elements the 
command table must be sent complete with all elements present. If the single password table 
is used to gain access to configuration items then the command can be sent alone without 
optional settings. The command options are: 
0 = No Action 1=Set kWh Register
2=Set kVARh Register 3=Set kVAh Register
4= Set kAh Register  5= Clear All Energy Registers
6=Set Status 1 Count 7=Set Status 2 Count
8=Set Status 3 Count  9=Set Status 4 Count
10=Force KYZ Output On  11=Force KYZ Output Off
12=Remove Force from KYZ  13=Force Relay 1 Output On
14=Force Relay 1 Output Off  15=Remove Force from Relay 1
16=Force Relay 2 Output On  17=Force Relay 2 Output Off
18=Remove Force from Relay 2  19=Force Relay 3 Output On
20=Force Relay 3 Output Off  21=Remove Force from Relay 3
22=Restore Factory Defaults  23=Reset Power Monitor  System
IMPORTANT: If a command is received that is not supported by your catalog number the 
command is ignored.
IMPORTANT: Output forcing (command options 10…21) is not permitted if an I/O 
connection (for example, Exclusive Owner, Data) is active. If an I/O connection is active and 
the configuration instance exists in the Logix Designer application, Command Word One 
options 1…23 are not permitted. 
0 0…23
1 Real Command Word Two 0 = No Action  1 = Clear Min/Max Records 
2 = Store and clear current Load Factor Record  3 = Clear Load Factor Log
4 = Store and clear current TOU Record  5 = Clear TOU Log
6 = Clear Setpoint Log  7 = Clear Setpoint accumulators
8 = Clear Error Log  9 = Clear Energy Log
10 = Clear Data Log  11 = Perform Wiring Diagnostics
12 = Log Off  13 = Clear Trigger Data Log 
14 = Trigger Waveform  15 = Clear Waveform 
16 = Metering Data Snapshot  17 = Clear Power Quality Log 
18 = Clear Setpoint Logic Gate Accumulators  19 = Reserved for future use
IMPORTANT: If a command is received that is not supported by your catalog number the 
command is ignored. 
0 0…18
2 Real Clear Single Min/Max 
Records
When invoking the Min/Max Clear command, this value can be sent to specify a single 
parameter. If clearing all values this is not required.
0 = Clear All Parameters
1= Clear the 1st Min/Max Record
2= Clear the 2nd Min/Max Record…To the end of the Min/Max Parameters
0 0…82 (M5, M6)
0…207 (M8)