Rockwell Automation Publication 1426-UM001J-EN-P - August 2019 369
PowerMonitor 5000 Unit Data Tables Appendix A
3 Real Clear Single Setpoint or
Logic Gate Accumulator
When invoking the Setpoint or Setpoint Logic Gate Accumulator Clear command this value
can be sent to specify a single parameter. If clearing all values this is not required.
0 = Clear All Accumulators
1= Clear the 1st time accumulator
2= Clear the 2nd time accumulator
20= Clear the 20th time accumulator
0 0…10 (M5);
0…10,
logic gate
accumulator,
0…20 setpoints
(M6 and M8)
4 Real Status 1 Count x M
Register Set Value
Status 1 Count Register Start Value x 1,000,000 0 0…9,999,999
5 Real Status 1 Count X 1
Register Set Value
Status 1 Count Register Start Value x 1 0 0…999,999
6 Real Status 2 Count x M
Register Set Value
Status 2 Count Register Start Value x 1,000,000 0 0…9,999,999
7 Real Status 2 Count X 1
Register Set Value
Status 2 Count Register Start Value x 1 0 0…999,999
8 Real Status 3 Count x M
Register Set Value
Status 3 Count Register Start Value x 1,000,000 0 0…9,999,999
9 Real Status 3 Count X 1
Register Set Value
Status 3 Count Register Start Value x 1 0 0…999,999
10 Real Status 4 Count x M
Register Set Value
Status 4 Count Register Start Value x 1,000,000 0 0…9,999,999
11 Real Status 4 Count X 1
Register Set Value
Status 4 Count Register Start Value x 1 0 0…999,999
12 Real GWh Fwd Register Set
Value
Sets the GWh Fwd Register to the desired Value 0 0…9,999,999
13 Real kWh Fwd Register Set
Value
Sets the kWh Fwd Register to the desired Value 0 0…999,999
14 Real GWh Rev Register Set
Value
Sets the GWh Rev Register to the desired Value 0 0…9,999,999
15 Real kWh Rev Register Set
Value
Sets the kWh Rev Register to the desired Value 0 0…999,999
16 Real GVARh Fwd Register Set
Value
Sets the GVARh Fwd Register to the desired Value 0 0…9,999,999
17 Real kVARh Fwd Register Set
Value
Sets the kVARh Fwd Register to the desired Value 0 0…999,999
18 Real GVARh Rev Register Set
Value
Sets the GVARh Rev Register to the desired Value 0 0…9,999,999
19 Real kVARh Rev Register Set
Value
Sets the kVARh Rev Register to the desired Value 0 0…999,999
20 Real GVAh Register Set Value Sets the GVAh Register to the desired Value 0 0…9,999,999
21 Real kVAh Register Set Value Sets the kVAh Register to the desired Value 0 0…999,999
22 Real GAh Register Set Value Sets the GAh Register to the desired Value 0 0…9,999,999
23 Real kAh Register Set Value Sets the kAh Register to the desired Value 0 0…999,999
24 Real Clear Waveform File ID Waveform file identity
0 = Clear All
If the identity is not known, the command is ignored.
00999
25 Real GWh Net Register Set
Value
Sets the GWh Net Register to the desired Value. 0 ±0…9,999,999
26 Real kWh Net Register Set
Value
Sets the kWh Net Register to the desired Value. 0 ±0…999,999
Table 131 - Command.System_Registers Data Table (continued)
Element
Number
Type Tag Name Description Default Range