370 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Appendix A PowerMonitor 5000 Unit Data Tables
Command.Controller_Interface
27 Real GVARh Net Register Set
Value
Sets the GVARh Net Register to the desired Value. 0 ±0…9,999,999
28 Real kVARh Net Register Set
Value
Sets the kVARh Net Register to the desired Value. 0 ±0…999,999
29…44 Real Reserved For future use. 0 0
Table 131 - Command.System_Registers Data Table (continued)
Element
Number
Type Tag Name Description Default Range
Table 132 - Table Properties
CIP Instance Number 839
PCCC File Number N48
No. of Elements 16
Length in Words 16
Data Type Int16
Data Access Write Only
Table 133 - Command.Controller_Interface Data Table
Element
Number
Type Tag Name Description Default Range
0 Int16 Controller_Command_Word Bit 0 = When this bit is written to the power monitor it signals the end of the demand period.
The power monitor resets the bit to 0 and sends the end of demand broadcast to all of the
slaves configured for the master/slave demand system. The power monitor must be
configured as a ‘Master’ for external demand pulse input.
Bit 1…Bit 15 = Reserved
001
1…15 Int16 Reserved Future Use 0 0