188 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Chapter 7 Logic Functions
Setup
The setup parameters for pulse totalizing and scaling are in the
Configuration.System.General
table on page 293 and are summarized in the
following section.
Log_Status_Input_Changes
These values are the choices:
0 = Disable recording of status input changes into the event log
1 = Enable recording of event input changes into the event log
Status_Input_1_Input_Scale
Status_Input_2_Input_Scale
Status_Input_3_Input_Scale
Status_Input_4_Input_Scale
When a status pulse is received, the count is increased by the scale factor. (Input
pulse * input scale) added to total status count.
Setup for demand EOI synchronization is described in Basic Metering
on
page 71.
Status
Status input status is reported by the state of the following Boolean tags, found in
the Status.DiscreteIO
table on page 342. For each tag, 0 = false, 1 = true.
Status_Input_1_Actuated
Status_Input_2_Actuated
Status_Input_3_Actuated
Status_Input_4_Actuated
The scaled value of status input counters are reported in the following tags, found
in the MeteringResults.Energy_Demand
table on page 375.