Rockwell Automation Publication 1426-UM001J-EN-P - August 2019 293
PowerMonitor 5000 Unit Data Tables Appendix A
Configuration.System.General
Table 56 - Table Properties
CIP Instance Number 803
PCCC File Number F12
No. of Elements 50
Length in Words 100
Data Type Real
Data Access Read/Write
Table 57 - Configuration.System.General Data Table
Element 
Number
Type Tag Name Description Default Range
0 Real Log_Status_Input_Changes 0=Disable recording of status input changes into the event log
1=Enable recording of event input changes into the event log
00…1
1 Real Use_Daylight_Savings_Correction 0 = Disable Daylight Savings
1 = Enable Daylight Savings
00…1
2RealDaylight_Savings_Month/Week/
Day_Start
This is the day that the power monitor adds an hour to the time. This feature also 
looks at Ethernet SNTP offset and corrects for Daylight Savings.
Example:  040107 = April/1st week/Saturday
Month Settings:
01 = January…
12 = December
Week Settings:
01 = 1st week…
05 = Last Week
Day of the Week Settings:
01 = Sunday…
07 = Saturday
030201 
March, 
2nd, 
Sunday
010101… 
120507
3 Real Hour_of_Day_Start The hour of day the daylight savings adjustment is made to add an hour. 2 0…23
4 Real Return_from_Daylight_Savings_
Month/Week/Day
This is the day that the power monitor subtracts an hour from the time. This feature 
also looks at Ethernet SNTP offset and corrects for the return from Daylight Savings.
Month Settings:
01 = January…
12 = December
Week Settings:
01 = 1st week…
05 = Last Week
Day of the Week Settings:
01 = Sunday…
07 = Saturday
110101 
November, 
1st, Sunday
010101… 
120507
5 Real Hour_of_Day_End The hour of day the daylight savings adjustment is made to subtract an hour. 2 0…23
6 Real KYZ_Solid_State_Output_
Parameter
The parameter selected pulses the KYZ output at a rate that equals the parameter 
value divided by KYZ scale.
0 = Setpoint Control
1 = Wh Fwd
2 = Wh Rev
3 = VARh Fwd
4 = VARh Rev
5 = VAh
6 = Ah
00…6