292 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Appendix A PowerMonitor 5000 Unit Data Tables
13 Real Demand_Period_Length
(Minutes)
Specifies the desired period for demand calculations. When set to 0 there is no
projected demand calculations. If the internal timer is selected a setting of 0 turns the
demand function off.
15 0…99
14 Real Number_Demand_Periods Specifies the number of demand periods to average for demand measurement. 1 1…15
15 Real Forced_Demand_Sync_Delay When the power monitor is configured for external demand control the unit delays for
xxx seconds after the expected control pulse has not been received. The demand
period starts over and a record is recorded in the event log.
0 = Wait forever
1…900 = Wait this many seconds before starting a new demand period
IMPORTANT: This setting becomes active when an external input is used to end the
demand period.
10 0…900
16…32 Real Reserved 00
Table 55 - Configuration.Metering.Basic Data Table (continued)
Element
Number
Type Tag Name Description Default Range