Chapter 9 Communication
• [ModuleName]:I, the Input or Scheduled Read tag
See Appendix A
 for the content of these data tables. When the module is first 
added to the Logix project, the [ModuleName]:C tag is populated with default 
configuration values. When the connection is opened, the configuration tag is 
written to the power monitor and over-writes any existing configuration. The 
module properties of the Add-on Profile are the interface to view and edit the 
values in the configuration tag.
With an exclusive owner connection active, the following capabilities and 
restrictions apply:
• Only the owner controller is permitted to modify the power monitor 
configuration. You can use the Logix Designer application and the module 
properties dialog box to view and edit the power monitor configuration.
• The owner controller can read the Input tag elements in its logic and write 
the Output tag elements in its logic.
• You can use Logix Designer application online with the owner controller 
to force inputs and outputs that are configured for native EtherNet/IP 
control in the power monitor.
• If the connection is lost, the Default_State_on_Comm_Loss parameter 
determines the behavior of each output.
IMPORTANT If the module definition is set to a data connection, but the configuration 
method is set to external means, the configuration tag is not created. In this 
case, the device can be configured by using the web interface, software, or 
by explicit message to the configuration tables.