264 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Chapter 9 Communication
The second sample message instruction reads a single value from the electrical 
energy object. This message calls the Get_Attribute_Single service (service code 
0x0E) for the Base Energy Object (Class code 0x4E), to read the Total Energy 
Odometer, attribute 9.
The data is returned in the correct ‘odometer’ format of five integers that are 
scaled by powers of 10. In this example, the total energy value is 1,471.371 kWh.