Rockwell Automation Publication 1426-UM001J-EN-P - August 2019 273
PowerMonitor 5000 Unit Data Tables Appendix A
6 2 Int16 SetPoint11_20Status Actuation Status of Setpoints 11 through 20 0…65535
Bit 0 SetPoint11Active 1 Indicates the setpoint is Active 0 or 1
Bit 1 SetPoint12Active 1 Indicates the setpoint is Active 0 or 1
Bit 2 SetPoint13Active 1 Indicates the setpoint is Active 0 or 1
Bit 3 SetPoint14Active 1 Indicates the setpoint is Active 0 or 1
Bit 4 SetPoint15Active 1 Indicates the setpoint is Active 0 or 1
Bit 5 SetPoint16Active 1 Indicates the setpoint is Active 0 or 1
Bit 6 SetPoint17Active 1 Indicates the setpoint is Active 0 or 1
Bit 7 SetPoint18Active 1 Indicates the setpoint is Active 0 or 1
Bit 8 SetPoint19Active 1 Indicates the setpoint is Active 0 or 1
Bit 9 SetPoint20Active 1 Indicates the setpoint is Active 0 or 1
Bit 10…15 Reserved Future Use 0
8 2 Int16 DiscreteOutputStatus Discrete Output status  0…65535
Bit 0 KYZLogicState KYZ Logic State 0 or 1
Bit 1 R1LogicState Relay 1 Logic State 0 or 1
Bit 2 R2LogicState Relay 2 Logic State 0 or 1
Bit 3 R3LogicState Relay 3 Logic State 0 or 1
Bit 4 KYZReadback Indicates Output KYZ Energized 0 or 1
Bit 5 KYZForcedOn Software Control Forced On KYZ 0 or 1
Bit 6 KYZForcedOff Software Control Forced Off KYZ 0 or 1
Bit 7 R1Readback Indicates Output Relay 1 Energized 0 or 1
Bit 8 R1ForcedOn Software Control Forced On Relay 1 0 or 1
Bit 9 R1ForcedOff Software Control Forced Off Relay 1 0 or 1
Bit 10 R2Readback Indicates Output Relay 2 Energized 0 or 1
Bit 11 R2ForcedOn Software Control Forced On Relay 2 0 or 1
Bit 12 R2ForcedOff Software Control Forced Off Relay 2 0 or 1
Bit 13 R3Readback Indicates Output Relay 3 Energized 0 or 1
Bit 14 R3ForcedOn Software Control Forced On Relay 3 0 or 1
Bit 15 R3ForcedOff Software Control Forced Off Relay 3 0 or 1
10 2 Int16 Year The currrent year 2010 2010…2100
12 2 Int16 Month_Day The current month and day 101 0101…1231
14 2 Int16 Hour_Minute The current hour and minute of the day 0 0000…2359
16 2 Uint16 Seconds_Milliseconds The current seconds and milliseconds 0 00000…59999
18 2 Int16 Reserved Future Use 0
20 4 Int32 Metering_Iteration_Num Metering iteration number 0 0…65535
24 2 Int16 PFLeadLag L1 lead or lag indicator for power factor 1 = leading, -1 = lagging -1…1
Table 41 - ScheduledData.Input Data Table (continued)
Start 
Byte
Size Type Tag Name Description Units Range