Rockwell Automation Publication 1426-UM001J-EN-P - August 2019 299
PowerMonitor 5000 Unit Data Tables Appendix A
Configuration.Setpoints_1_5
Table 62 - Table Properties
CIP Instance Number 807
PCCC File Number F16
No. of Elements 50
Length in Words 100
Data Type Real
Data Access Read/Write
Table 63 - Configuration.Setpoints_1_5 Data Table
Element 
Number
Type Tag Name Description Default Range
0 Real Parameter 
Selection 1
Selection of the input parameter from the Setpoint Parameter Selection List. 0 0…105 (M5, M6)
0…230 (M8)
1 Real Reference Value 
1
Used when Evaluation type is 2 = Percent of Reference 0 -10,000,000
…10,000,000
2 Real Test Condition 1 0 = Disabled
1 = Less Than
2 = Greater Than
3 = Equals
0 0…3
3 Real Evaluation Type 1 0 = Magnitude
1 = State
2 = Percent of Reference (not supported in the M5 model)
3 = Percent of Sliding Reference (not supported in the M5 model)
00…3
4 Real Threshold 1 The value, percent, or state that triggers the output action. 0 -10,000,000…
10,000,000
5 Real Hysteresis 1 The value in magnitude or percent of reference at which the output action is deasserted.
Example: A less than condition deasserts at (threshold + hysteresis), a greater than condition 
deasserts at (threshold - hysteresis).
0 0…10,000,000
6 Real Assert Delay 
Seconds 1
The amount of time to delay the output action after a setpoint trigger occurs. Minimum equals 
realtime update rate setting.
0 0.000…3600
7 Real Deassert Delay 
Seconds 1
The amount of time to delay deassertion after the setpoint trigger releases. Minimum equals 
realtime update rate setting.
0 0.000…3600
8 Real Parameter 
Selection 2
Selection of the input parameter from the Setpoint Parameter Selection List. 0 0…105 (M5, M6)
0…230 (M8)
9 Real Reference Value 
2
Used when Evaluation type is 2 = Percent of Reference 0 -10,000,000
…10,000,000
10 Real Test Condition 2 0 = Disabled
1 = Less Than
2 = Greater Than
3 = Equals
0 0…3
11 Real Evaluation Type 2 0 = Magnitude
1 = State
2 = Percent of Reference (not supported in the M5 model)
3 = Percent of Sliding Reference (not supported in the M5 model)
00…3
12 Real Threshold 2 The value, percent, or state that triggers the output action. 0 -10,000,000…
10,000,000