30 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Chapter 2 Install the PowerMonitor 5000 Unit
Status Inputs
Up to four dry (non-powered) contacts can be connected to the
PowerMonitor 5000 unit status inputs. The status input derives 24V DC power
from its internal power supply.
Connect status inputs by using shielded, twisted-pair cable with the shield
connected to the ground bus or other low-impedance earth ground at the contact
end only. The diagram indicates typical status input wiring.
Figure 20 - Status Inputs
KYZ and Relay Outputs
The KYZ solid-state relay output can be connected to an external pulse
accumulator or controller. Relay outputs can be used for control of loads,
switching of circuit breakers, signaling, and other applications. The external
device or circuit must provide wetting voltage. The KYZ output is designed for
low-current switching. The diagram indicates typical KYZ and relay output
wiring.
Figure 21 - KYZ and Relay Outputs
S1
S2
S3
S4
Scom
Scom
Ground
Ground
Contact 1
Contact 2
Contact 3
Contact 4
PowerMonitor 5000
(COM)
( + ) ( - )
( + ) ( - )
(N.C.)
(N.C.)
(N.O.)
(N.O.)
(COM)
Z
K
Y
Rn C
Rn com
Rn O
PowerMonitor 5000
(equivalent circuit)
PowerMonitor 5000
(typical for R1, R2, and R3)
Wetting Power
Supply
Max 240V AC/DC
(by user)
Wetting Power
Supply
Max 240V AC/DC
(by user)
Pulse Accumulator
or Controller
(by user)
Controlled Load
(by user)
IN 1
COM
T1
T2