304 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Appendix A PowerMonitor 5000 Unit Data Tables
32 Real Parameter
Selection 10
Selection of the input parameter from the Setpoint Parameter Selection List. 0 0…105 (M5, M6)
0…230 (M8)
33 Real Reference Value
10
Used when Evaluation type is 2 = Percent of Reference 0 -10,000,000
…10,000,000
34 Real Test Condition 10 0 = Disabled
1 = Less Than
2 = Greater Than
3 = Equals
0 03
35 Real Evaluation Type
10
0 = Magnitude
1 = State
2 = Percent of Reference (not supported in the M5 model)
3 = Percent of Sliding Reference (not supported in the M5 model)
003
36 Real Threshold 10 The value, percent, or state that triggers the output action. 0 -10,000,000…
10,000,000
37 Real Hysteresis 10 The value in magnitude or percent of reference at which the output action is deasserted.
Example: A less than condition deasserts at (threshold + hysteresis), a greater than condition
deasserts at (threshold - hysteresis).
0 0…10,000,000
38 Real Assert Delay
Seconds 10
The amount of time to delay the output action after a setpoint trigger occurs. Minimum equals
realtime update rate setting.
0 0.000…3600
39 Real Deassert Delay
Seconds 10
The amount of time to delay deassertion after the setpoint trigger releases. Minimum equals
realtime update rate setting.
0 0.000…3600
40…49 Real Reserved Future Use 0 0
Table 65 - Configuration.Setpoints_6_10 Data Table (continued)
Element
Number
Type Tag Name Description Default Range