Rockwell Automation Publication 1426-UM001J-EN-P - August 2019 311
PowerMonitor 5000 Unit Data Tables Appendix A
Configuration.Setpoint_Logic (M6 and M8 Model)
Table 70 - Table Properties
CIP Instance Number 811
PCCC File Number N20
No. of Elements 100
Length in Words 100
Data Type Int16
Data Access Read/Write
Table 71 - Configuration.Setpoint_Logic Data Table
Element 
Number
Type Tag Name Description Default Range
0 Int16 Logic Level 1 
Gate 1 Function
Selects the logic type 
0 = disabled
1 = AND
2 = NAND
3 = OR
4 = NOR
5 = XOR
6 = XNOR
IMPORTANT: XOR and XNOR use Inputs 1 and 2 only.
00…6
1 Int16 L1_G1 Input 1 Selects the first input parameter for the gate.  Each gate has four inputs.  
0 = Disabled
1 = Setpoint 1
2 = Setpoint 2
3 = Setpoint 3
…
20 = Setpoint 20
IMPORTANT: Negative numbers invert the input.
0 -20…20
2 Int16 L1_G1 Input 2 Selects the second input parameter for the gate.  Each gate has four inputs.   
0 = Disabled
1 = Setpoint 1
2 = Setpoint 2
3 = Setpoint 3
…
20 = Setpoint 20
IMPORTANT: Negative numbers invert the input.
0 -20…20
3 Int16 L1_G1 Input 3 Selects the third input parameter for the gate.  Each gate has four inputs.   
0 = Disabled
1 = Setpoint 1
2 = Setpoint 2
3 = Setpoint 3
…
20 = Setpoint 20
IMPORTANT: Negative numbers invert the input.
0 -20…20
4 Int16 L1_G1 Input 4 Selects the fourth input parameter for the gate.  Each gate has four inputs.  
0 = Disabled
1= Setpoint 1
2 = Setpoint 2
3 = Setpoint 3
…
20 = Setpoint 20  IMPORTANT: Negative numbers invert the input.
0 -20…20