320 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Appendix A PowerMonitor 5000 Unit Data Tables
Configuration.Setpoint_Outputs
Table 72 - Table Properties
CIP Instance Number 812
PCCC File Number N21
No. of Elements 100
Length in Words 100
Data Type Int16
Data Access Read/Write
Table 73 - Configuration.Setpoint_Outputs Data Table
Element 
Number
Type Tag Name Description Default Range
0 Int16 Setpoint Output 
1 Input Source
Selects the source for output. Setpoint or gate output state.
0 = No source
1 = Setpoint 1
2 = Setpoint 2…
20 = Setpoint 20
21 = Level1_G1 …
30 = Level1_G10
1 0…10 (M5)
0…30 (M6, M8)
1 Int16 Setpoint Output 
1 Action
Selects the output action to perform when setpoint is asserted. See the Setpoint Output Action List
. 0 0…19 (M5)
0…30 (M6, M8)
2 Int16 Setpoint Output 
2 Input Source
Selects the source for output. Setpoint or gate output state.
0 = No source
1 = Setpoint1
2 = Setpoint 2…
20 = Setpoint 20
21 = Level1_G1 …
30 = Level1_G10
2 0…10 (M5)
0…30 (M6, M8)
3 Int16 Setpoint Output 
2 Action
Selects the output action to perform when setpoint is asserted. See the Setpoint Output Action List
. 0 0…19 (M5)
0…30 (M6, M8)
4 Int16 Setpoint Output 
3 Input Source
Selects the source for output. Setpoint or gate output state.
0 = No source
1 = Setpoint1
2 = Setpoint 2…
20 = Setpoint 20
21 = Level1_G1 …
30 = Level1_G10
3 0…10 (M5)
0…30 (M6, M8)
5 Int16 Setpoint Output 
3 Action
Selects the output action to perform when setpoint is asserted. See the Setpoint Output Action List
. 0 0…19 (M5)
0…30 (M6, M8)
6 Int16 Setpoint Output 
4 Input Source
Selects the source for output. Setpoint or gate output state.
0 = No source
1 = Setpoint1
2 = Setpoint 2…
20 = Setpoint 20
21 = Level1_G1 …
30 = Level1_G10
4 0…10 (M5)
0…30 (M6, M8)
7 Int16 Setpoint Output 
4 Action
Selects the output action to perform when setpoint is asserted. See the Setpoint Output Action List
. 0 0…19 (M5)
0…30 (M6, M8)