EasyManua.ls Logo

Rockwell Automation Allen-Bradley PowerMonitor 5000 Unit - Page 332

Rockwell Automation Allen-Bradley PowerMonitor 5000 Unit
514 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
332 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Appendix A PowerMonitor 5000 Unit Data Tables
Configuration.TriggerSetpointInfoFile (M6 and M8 model)
Configuration.TriggerData_Log (M6 and M8 model)
Table 90 - Table Properties
CIP Instance Number 867
PCCC File Number ST76
No. of Elements 1
Length in Words 32
Data Type String
Data Access Write Only
Table 91 - Configuration.TriggerSetpointInfoFile Data Table
Element
Number
Type Tag Name Description Default Range
0 String Trigger_Setpoint
_Log_File
A single entry table for a 64 character Filename entry 0 64 bytes
Table 92 - Table Properties
CIP Instance Number 822
PCCC File Number N31
No. of Elements 10
Length in Words 10
Data Type Int16
Data Access Read/Write
Table 93 - Configuration.TriggerData_Log Data Table
Element
Number
Type Tag Name Description Default Range
0 Int16 Trigger_Mode Selects how records are saved.
0= Fill and stop recording when log is full.
1= Overwrite when log is full starting with the earliest record.
101
1 Int16 TriggerData_Length_s TriggerData log length from 1s to 10s 1s 1…10s
2 Int16 TriggerData_Parameter_1 Selection of parameter or default to be logged in the trigger data log. 5 1…184
3 Int16 TriggerData_Parameter_2 9 0…184
4 Int16 TriggerData_Parameter_3 14 0…184
5 Int16 TriggerData_Parameter_4 15 0…184
6 Int16 TriggerData_Parameter_5 19 0…184
7 Int16 TriggerData_Parameter_6 23 0…184
8 Int16 TriggerData_Parameter_7 27 0…184
9 Int16 TriggerData_Parameter_8 39 0…184

Table of Contents

Related product manuals