Rockwell Automation Publication 1426-UM001J-EN-P - August 2019 359
PowerMonitor 5000 Unit Data Tables Appendix A
5 Int16 Input_I2_Mapping This parameter logically maps a physical current channel to I2.
1 = I1
2 = I2
3 = I3
-1 = I1 inverted
-2 = I2 inverted
-3 = I3 inverted
2-3-1
1…3
6 Int16 Input_I3_Mapping This parameter logically maps a physical current channel to I3.
1 = I1
2 = I2
3 = I3
-1 = I1 inverted
-2 = I2 inverted
-3 = I3 inverted
3-3-1
1…3
7 Int16 Last_Cmd_Rejection_Status 0 = No rejection
1 = Rejected see rejection status
001
8 Int16 Rejection_Information 0 = No information
1 = Selected range is incomplete
2 = Command is already active. Use command 5 to start over
3 = Two like inputs wired to one terminal
4 = Invalid Input parameter
004
9…13 Int16 Reserved Future Use 0 0
Table 121 - Status.Wiring_Corrections Data Table (continued)
Element
Number
Type Tag Name Description Default Range