Rockwell Automation Publication 1426-UM001J-EN-P - August 2019 387
PowerMonitor 5000 Unit Data Tables Appendix A
LoggingResults.Event_Log
Table 158 - Table Properties
CIP Instance Number 857
PCCC File Number N66
No. of Elements 9
Length in Words 9
Data Type Int16
Data Access Read Only
Table 159 - LoggingResults.Event_Log Data Table
Element 
Number
Type Tag Name Description Unit Range
0 Int16 Event_Record_Identifier Used to verify record sequence when returning multiple records. 0…100
1 Int16 Event_Timestamp_Year  The year when the record was recorded. YYYY 2010…2100
2 Int16 Event_Timestamp_Mth_Day The month and day when the record was recorded. MMDD 11…1231
3 Int16 Event_Timestamp_Hr_Min The hour and minute when the record was recorded. HHMM 0…2359
4 Int16 Event_Timestamp_Sec_ms The seconds and milliseconds when the record was recorded. SSms 0…59,999
5 Int16 Event Type Indicates the type of event that has occurred. 0…65535
6 Int16 General Code Indicates general information about the status event. 0…65535
7 Int16 Information Code Indicates specific information about the status event. 0…65535
8 Int16 Reserved Reserved 0