392 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Appendix A PowerMonitor 5000 Unit Data Tables
LoggingResults.TriggerData_Header (M6 and M8 model)
Table 168 - Table Properties
CIP Instance Number 862
PCCC File Number F71
No. of Elements 15
Length in Words 30
Data Type Real
Data Access Read Only
Table 169 - LoggingResults. TriggerData_Header Data Table
Element
Number
Type Tag Name Description Unit Range
0 Real Record_Indicator Indicates the significance of data in the record 0 = No record returned
1= the record contains
parameter values
2 = the record contains general
information of the log file being
retrieved, reference to each item
description in the data table
3= log file not found
1 Real TriggerHeader_Record
_Identifier
Internal unique record number, if Record_Indicator = 1
Total records number in the log file, if Record_Indicator = 2.
# +/- 0…9.999E15
2 Real TriggerAction_
Timestamp_Year
The year when the trigger action occurred. YYYY 2010…2100
3 Real TriggerAction_
Timestamp_Month_
Day
The month and day when the trigger action occurred. MMDD 0101…1231
4 Real TriggerAction_
Timestamp_Hour_
Minute
The hour and minute when the trigger action occurred. hhmm 0000…2359
5 Real TriggerAction_
Timestamp_Sec_mS
The seconds and milliseconds when the trigger action occurred. ssmS 00000…59999
6 Real SetpointNumber Setpoint number of trigger # 1…30
7 Real ParameterSelection or
Logic_Gate_Type
ParameterSelection if SetpointNumber = (1…20)
Logic_Gate_Type if SetpointNumber = (21 …30)
#See description
8 Real ReferenceValue or
Logic_Input_1
ReferenceValue if SetpointNumber = (1…20)
Logic_Input_1 if SetpointNumber = (21… 30)
#See description
9 Real TestCondition or
Logic_Input_2
TestCondition if SetpointNumber = (1…20)
Logic_Input_2 if SetpointNumber = (21 …30)
#See description
10 Real EvaluationType or
Logic_Input_3
EvaluationType if SetpointNumber = (1…20)
Logic_Input_3 if SetpointNumber = (21…30)
#See description
11 Real Threshold or
Logic_Input_4
Threshold if SetpointNumber = (1… 20)
Logic_Input_4 if SetpointNumber = (21… 30)
#See description
12 Real Hysteresis Hysteresis for setpoint # 0…10,000,000
13 Real AssertDelay_s AssertDelay for setpoint s 0.000…3600
14 Real DeassertDelay_s DeassertDelay for setpoint s 0.000…3600