398 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Appendix A PowerMonitor 5000 Unit Data Tables
LoggingResults.EN50160_Weekly_Log (M8 only)
39 Real X_(28 + Order * 32) The returned value X_(h) for the spectral component specified by Channel 
at harmonic h 
X_(h) = RMS magnitude if Mag_Angle = 0
X_(h) = Angle if Mag_Angle = 1
+/- 0…9.999E15
40 Real X_(29 + Order * 32) +/- 0…9.999E15
41 Real X_(30 + Order * 32) +/- 0…9.999E15
42 Real X_(31 + Order * 32) +/- 0…9.999E15
Table 179 - LoggingResults. Waveform_Log Data Table (continued)
Element 
Number
Type Tag Name Description Unit Range
Table 180 - Table Properties
CIP Instance Number 874
PCCC File Number F83
No. of Elements 13
Length in Words 26
Data Type Real
Data Access Read only
Applies to M8 only
Table 181 - LoggingResults.EN50160_Weekly_Log Data Table
Element 
Number
Type Tag Name Description Units Range
0 Real Record_Number The record number of the log.  Record 1 is always the current record before 
being logged.
# 1….8
1 Real Log_Date   The Date this record was started. YYMMDD 0….999,999
2 Real Supply Voltage Range 1 Metering interval is 10 minutes; Conformance limit is +10% / - 10%; 
Conformance recommendation is 95%
% 0.00….100.00
3 Real Supply Voltage Range 2 Metering interval is 10 minutes; Conformance limit is +10% / - 15%; 
Conformance recommendation is 100%
% 0.00….100.00
4 Real Flicker Severity Plt Metering interval is 2 hours; Conformance limit is 1 or less; Conformance 
recommendation is 95%
% 0.00….100.00
5 Real Supply Voltage Unbalance Metering interval is 10 minutes; Conformance limit is 0% to 2%; 
Conformance recommendation is 95%
% 0.00….100.00
6 Real Individual Harmonic Voltage Metering interval is 10 minutes; Conformance limit is the table 1 of the 
EN50160 standard; Conformance recommendation is 95%
% 0.00….100.00
7 Real Voltage THD Metering interval is 10 minutes; Conformance limit is 8% or less; 
Conformance recommendation is 100%
% 0.00….100.00
8 Real Non Synchronous Power Freq. Range 1 Metering interval is 10 seconds; Conformance limit is +2% / -2%; 
Conformance recommendation is 95%
% 0.00….100.00
9 Real Non Synchronous Power Freq. Range 2  Metering interval is 10 seconds; Conformance limit is +15% / -15%; 
Conformance recommendation is 100%
% 0.00….100.00
10 Real 10_Minutes_Valid_Data_Counts Number of 10 minutes intervals without interruption flag set during 1 day # 0….999,999
11 Real 2_Hours_Valid_Data_Counts Number of 2 hours intervals without interruption flag set during 1 day # 0….999,999
12 Real 10_Seconds_Valid_Data_Counts Number of 10 seconds intervals without interruption flag set during 1 day # 0….999,999