Rockwell Automation Publication 1426-UM001J-EN-P - August 2019 401
PowerMonitor 5000 Unit Data Tables Appendix A
PowerQuality.RealTime_PowerQuality
Table 184 - Table Properties
CIP Instance Number 845
PCCC File Number F54
No. of Elements 56
Length in Words 112
Data Type Real
Data Access Read Only
Table 185 - PowerQuality.RealTime_PowerQuality Data Table
Element
Number
Type Tag Name Description Units Range
0 Real Metering Date Stamp Date of cycle collection MM:DD:YY MM:DD:YY 0…123,199
1 Real Metering Time Stamp Time of cycle collection HH:MM:SS HH:MM:SS 0…235,959
2 Real Metering Microsecond Stamp Microsecond of cycle collection uS 0.000…999,999
3 Real V1_Crest_Factor V1 crest factor 0…9.999E15
4 Real V2_Crest_Factor V2 crest factor 0…9.999E15
5 Real V3_Crest_Factor V3 crest factor 0…9.999E15
6 Real V1_V2_Crest_Factor V1 V2 crest factor 0…9.999E15
7 Real V2_V3_Crest_Factor V2 V3 crest factor 0…9.999E15
8 Real V3_V1_Crest_Factor V3 V1 crest factor 0…9.999E15
9 Real I1_Crest_Factor I1 crest factor 0…9.999E15
10 Real I2_Crest_Factor I2 crest factor 0…9.999E15
11 Real I3_Crest_Factor I3 crest factor 0…9.999E15
12 Real I4_Crest_Factor I4 crest factor 0…9.999E15
13 Real V1_IEEE_THD_% V1-N IEEE Total Harmonic Distortion % 0.00…100.00
14 Real V2_IEEE_THD_% V2-N IEEE Total Harmonic Distortion % 0.00…100.00
15 Real V3_IEEE_THD_% V3-N IEEE Total Harmonic Distortion % 0.00…100.00
16 Real VN_G_IEEE_THD_% VGN-N IEEE Total Harmonic Distortion % 0.00…100.00
17 Real Avg_IEEE_THD_V_% Average V1/V2/V3 to N IEEE Total Harmonic Distortion % 0.00…100.00
18 Real V1_V2_IEEE_THD_% V1-V2 IEEE Total Harmonic Distortion % 0.00…100.00
19 Real V2_V3_IEEE_THD_% V2-V3 IEEE Total Harmonic Distortion % 0.00…100.00
20 Real V3_V1_IEEE_THD_% V3-V1 IEEE Total Harmonic Distortion % 0.00…100.00
21 Real Avg_IEEE_THD_V_V_% Average IEEE THD for V1-V2, V2-V3, V3-V1 % 0.00…100.00
22 Real I1_IEEE_THD_% I1 IEEE Total Harmonic Distortion % 0.00…100.00
23 Real I2_IEEE_THD_% I2 IEEE Total Harmonic Distortion % 0.00…100.00
24 Real I3_IEEE_THD_% I3 IEEE Harmonic Distortion % 0.00…100.00
25 Real I4_IEEE_THD_% I4 IEEE Harmonic Distortion % 0.00…100.00
26 Real Avg_IEEE_THD_I_% Average I1/I2/I3 IEEE Total Harmonic Distortion % 0.00…100.00
27 Real V1_IEC_THD_% V1-N IEC Total Harmonic Distortion % 0.00…100.00
28 Real V2_IEC_THD_% V2-N IEC Total Harmonic Distortion % 0.00…100.00

Table of Contents