408 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Appendix A PowerMonitor 5000 Unit Data Tables
28 Real 3s_V3_V1_Magnitude Aggregated 3 second result V 0…9.999E15
29 Real 10m_V3_V1_Magnitude Aggregated 10 minute result V 0…9.999E15
30 Real 2h_V3_V1_Magnitude Aggregated 2 hour result V 0…9.999E15
31 Real CH1_Short_Term_Flicker_Pst Flicker short term result Pst 0.00…100.00
32 Real CH1_Long_Term_Flicker_Plt Flicker long term result Plt 0.00…100.00
33 Real CH2_Short_Term_Flicker_Pst Flicker short term result Pst 0.00…100.00
34 Real CH2_Long_Term_Flicker_Plt Flicker long term result Plt 0.00…100.00
35 Real CH3_Short_Term_Flicker_Pst Flicker short term result Pst 0.00…100.00
36 Real CH3_Long_Term_Flicker_Plt Flicker long term result Plt 0.00…100.00
37 Real CH1_Mains_Signaling_Voltage 3 second aggregation used for EN50160 V 0…9.999E15
38 Real CH2_Mains_Signaling_Voltage 3 second aggregation used for EN50160 V 0…9.999E15
39 Real CH3_Mains_Signaling_Voltage 3 second aggregation used for EN50160 V 0…9.999E15
40 Real 3s_Voltage_Unbalance Aggregated 3 second result % 0.00…100.00
41 Real 10m_Voltage_Unbalance Aggregated 10 minute result % 0.00…100.00
42 Real 2h_Voltage_Unbalance Aggregated 2 hour result % 0.00…100.00
43 Real 3s_Sag_Swell_Status_Flag A flag indicating the 3s result has been calculated during a Sag, Swell, or 
Interruption.
#0…1
44 Real 10m_Sag_Swell_Status_Flag A flag indicating the 10min result has been calculated during a Sag, Swell, 
or Interruption.
#0…1
45 Real 2h_Sag_Swell_Status_Flag A flag indicating the 2hr result has been calculated during a Sag, Swell, or 
Interruption.
#0…1
Table 193 - PowerQuality.EN61000_4_30_Aggregation Data Table (continued)
Element 
Number
Type Tag Name Description Units Range