Rockwell Automation Publication 1426-UM001J-EN-P - August 2019 425
PowerMonitor 5000 Unit Data Tables Appendix A
PowerQuality.EN61000_4_30 Harmonic and Interharmonic Group 
Results (M8 only)
These tables share the following properties.
The EN61000-4-30 Harmonic and Interharmonic Results data tables share a 
common structure. 
•Data Table Name: 
PowerQuality.<Interval>_<CH>_<Units>_RMS_<HDS/IHDS>
• Tag Name: <Interval>_<CH>_<Units>_RMS_<HDS/IHDS> 
(DC…50)
Table 211 - Table Properties
No. of Elements 54
Length in Words 108
Data Type Real
Data Access Read only
Applies to M8 only
Table 212 - Substitution Table
For: Substitute: To return these EN61000_4_30 results:
<Interval> 200mS 200mS interval group
3s 3 second interval group
10m 10 minute interval group
2h 2 hour interval group
<CH> V1_N Line 1 to Neutral voltage
V2_N Line 2 to Neutral voltage
V3_N Line 3 to Neutral voltage
VN_G Neutral to Ground voltage
V1_V2 Line 1 to Line 2 voltage
V2_V3 Line 2 to Line 3 voltage
V3_V1 Line 3 to Line 1 voltage
I1 Line 1 current
I2 Line 2 current
I3 Line 3 current
I4 Line 4 current
<Units> Volts Voltage
Amps Current
<HDS/IHDS> HDS Harmonic distortion subgroup
IHDS Interharmonic distortion subgroup