438 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Appendix C PowerMonitor 5000 Display Module, Series B Application Summary
1. To exit the application, press Exit.
The Main screen displays.
2. Press Communication.
The Communication screen displays.
3. To disable DHCP, press Disable DHCP.
4. Obtain an IP address for the PanelView 800 terminal.
5. Press Set Static IP Address and enter the IP address for the PanelView 800 
terminal.
6. After the IP address of the PanelView 800 terminal has been configured, 
return to the Main screen.
IMPORTANT If a terminal is set for DHCP and is not on a network or is on a network that 
does not have a DHCP server (or the server is not available), it automatically 
assigns itself an Automatic Private IP address (or auto IP address). The auto 
IP address is in the range of 169.254.0.0 through 169.254.255.255.
The terminal makes sure that the auto IP address is unique from any other 
auto IP address of other devices on the network. The terminal can now 
communicate with other devices on the network that have IP addresses in 
the 169.254.xxx.xxx range (and a subnet mask of 255.255.0.0).