Rockwell Automation Publication 1426-UM001J-EN-P - August 2019 485
EN 61000-4-30 Metering and Aggregation Appendix I
In general, only basic metering setup is required, except as noted otherwise in the
sections that follow.
5.4 Dips and swells A N/A
SN/A
BN/A
5.5 Interruptions A N/A
SN/A
BN/A
5.7 Unbalance A 0…5% U
2
, 0…5% U
0
S 0…5% U
2
B Specified by manufacturer
5.8 Voltage harmonics A 200% of class 3 of IEC 61000-2-4
S 200% of class 3 of IEC 61000-2-4
B 200% of class 3 of IEC 61000-2-4
5.9 Voltage interharmonics A 200% of class 3 of IEC 61000-2-4
S 200% of class 3 of IEC 61000-2-4
B 200% of class 3 of IEC 61000-2-4
5.10 Mains signaling voltage A 0…15% U
din
S 0…15% U
din
B 0…15% U
din
5.12 Under/overdeviation A N/A
SN/A
BN/A
Transient voltages IEC 61180 A 6 kV peak
SN/A
BN/A
Fast transients IEC 61000-4-4 A 4 kV peak
SN/A
BN/A
(1) Copyright by IEC. Used with permission.
(2) For safety requirements, EMC requirements, or climatic requirements, see product standards, for example, IEC 61557-12.
Table 236 - Influence Quantity Range
(1)
(2)