Rockwell Automation Publication 1426-UM001J-EN-P - August 2019 503
Glossary
Noise, Electrical Undesired broadband electrical signals superimposed on the power system 
voltage. 
Notching Periodic voltage distortion created by three-phase power electronic devices when 
current is commutated from one phase to another.
Ohm The unit of electrical resistance. One ohm is the value of resistance through 
which a potential difference of one volt maintains a current flow of one ampere.
Overvoltage An increase in the rms voltage greater than 110% of nominal for more than 1 
minute.
Peak Demand The highest average load over a utility specified time interval during a billing 
period. If there is no ratchet clause in the rate schedule, then the peak demand is 
also the billing demand.
Phasor Diagram A vector diagram that shows the magnitude and phase relationship of the 
voltages and currents in a three-phase system.
Polyphase Having or utilizing several phases. A polyphase power circuit has several 
(typically three) phases of alternating current with a fixed phase angle between 
phases.
Potential Transformer (PT) A transformer with the primary winding connected in parallel with the circuit 
whose voltage is to be measured or controlled. PTs are normally used to step 
down high-voltage potentials to lower levels acceptable to measuring 
instruments. Also known as voltage transformer (VT).
Potential Transformer Ratio The ratio of primary voltage divided by secondary voltage.
Power Factor The ratio of real power in watts of an alternating current circuit to the apparent 
power in volt-amperes. Also expressed as the cosine of the phase angle between 
the fundamental voltage that is applied to a load and the current passing through 
it.
Power Factor Correction Steps taken to raise the power factor by closely aligning the current to be in phase 
with the applied voltage. Most frequently, this process consists of added 
capacitance to increase the lagging power factor of inductive circuits.
Power Factor Penalty The charge utilities impose for operating at power factor below some rate 
schedule-specified level. This level ranges from a lagging power factor of 0.80 to 
unity. There are innumerable ways by which utilities calculate power factor 
penalties.
Power Quality Qualitatively, the fitness of electrical voltage to supply power to consuming 
devices. Quantitatively, the observed set of electrical characteristics at a given 
point on an electrical system as compared to a set of reference conditions.
Rapid Voltage Changes A rapid change is rms value between two steady-state conditions. The magnitude 
in the change is less than the sag or swell thresholds.